Outdated Sizing Logic Could Cost You
If your heat pump installer talks about "sizing for cooling load" or warns you about "oversized" systems, they're using outdated logic and it could cost you flexibility and money in the long run.
Here's what Xcel Energy actually requires, why it matters, and how to make sure your system is sized correctly.

The Old Way: Size for Cooling
For decades, HVAC contractors sized air conditioners based on cooling load: how much heat needs to be removed on the hottest summer days. This made sense when:
- AC was AC and furnaces were furnaces
- Heat pumps were rare in cold climates
- Backup heat was cheap (natural gas)
The rule was simple: Calculate how many BTUs you need to cool the house on a 95 degree F day, pick a system that matches, done.
Many contractors still do this with heat pumps. It's what they learned. It's habit.
The problem: A system sized for cooling is often too small for heating. When temperatures drop, the heat pump can't keep up, and your backup heat kicks in earlier and runs longer than it should.
The New Way: Size for Heating
Xcel Energy's 2025 Quality Installation requirements are explicit about this for cold climate heat pumps:
"Inverter driven/variable speed heat pumps (includes Xcel's definition of cold climate heat pumps): Size for heating load. No oversizing penalty."
This means: If you're installing a cold climate heat pump in Colorado, the system should be sized to handle your heating load. How many BTUs you need on the coldest winter nights.

But Won't an Oversized Heat Pump Short-Cycle?
You might hear this concern: "If you size for heating, the system will be oversized for cooling and will short-cycle, reducing efficiency and lifespan."
This argument doesn't apply to variable-speed heat pumps.
Variable-speed (inverter-driven) equipment doesn't short-cycle. It runs anywhere from 20% to 100% capacity. On a mild day, it runs slower. On a hot day, it ramps up. The compressor modulates continuously rather than banging on and off.
This is exactly why Xcel's requirements state: "Size for heating load. No oversizing penalty."
A 5-ton variable-speed heat pump on a 75 degree F day doesn't cycle. It runs at 30-40% capacity, maintaining temperature smoothly. Short-cycling is a single-stage equipment problem, not a variable-speed one.
If someone is warning you about "oversized" variable-speed heat pumps, they either don't understand how the technology works or they're justifying a smaller (cheaper) system that won't meet your heating needs.
Why Size for Full Heating Capacity?
Here's the honest truth: Gas is currently cheaper to operate than electric in Colorado. If you're running backup heat frequently, it's not a disaster for your wallet right now.
So why size the heat pump to handle the full heating load?
Future-proofing. Energy prices change. Colorado's Clean Heat Plan is pushing utilities toward electrification. Gas rates may rise. Electric rates may fall as renewables scale. Having a heat pump that can do all the heating means you're ready either way.
Flexibility. A properly sized system lets you choose. Run the heat pump down to -10 degrees F if electricity is cheap. Switch to gas backup earlier if gas is cheaper. You have options.
The alternative is permanent limitation. An undersized heat pump will always need backup below a certain temperature. You can't fix that without replacing equipment.
The real risk is undersizing. Some installers recommend smaller systems to avoid "oversizing concerns." This leaves homeowners permanently reliant on backup heat for a significant portion of winter, with no way to change that if economics shift.

What This Means in Practice
Let's say your home needs:
- Cooling load: 36,000 BTU (3 tons)
- Heating load: 54,000 BTU (4.5 tons)
Old-School Sizing (for cooling)
- Install a 3-ton heat pump
- On cold days, heat pump maxes out at 36,000 BTU
- Backup heat covers the remaining 18,000 BTU
- Result: Backup runs frequently, limited flexibility
Xcel-Compliant Sizing (for heating)
- Install a 4.5-5 ton heat pump
- On cold days, heat pump covers 54,000 BTU
- Backup heat rarely needed (only extreme cold)
- Result: Heat pump does 95%+ of the work, full flexibility
The Technical Requirements (Manual J and Manual S)
Xcel requires contractors to follow ACCA standards for load calculations and equipment selection:
Manual J = Load calculation. How many BTUs does your house actually need for heating and cooling? This accounts for:
- Square footage and layout
- Insulation levels
- Window area and orientation
- Air leakage
- Colorado's specific climate data (ASHRAE 99.6% design conditions)
Manual S = Equipment selection. Given the load calculation, what equipment should you install?
For cold climate heat pumps, Manual S Part N2.3.4.1 specifies:
- Heating size factor greater than or equal to 1.0 (system meets or exceeds heating load)
- Cooling size factor less than or equal to 0.8 (system may exceed cooling load, that's fine for variable-speed)
The contractor must document the switchover temperature (when backup heat kicks in) and backup heat type (electric or gas).
What Contractors Get Wrong
1. Sizing for cooling out of habit
Old-school contractors default to cooling-based sizing because that's how they've always done it. They may not realize Xcel's requirements specify heating-based sizing for variable-speed equipment.
Red flag: If your contractor says "we size for cooling load," ask why, and whether they're following Xcel's 2025 QI requirements.
2. Warning about "oversized" variable-speed systems
This reveals a misunderstanding of the technology. Variable-speed systems modulate; they don't short-cycle. Xcel explicitly says there's no oversizing penalty.
Red flag: If someone warns you about oversizing while quoting a smaller system, ask them to explain how variable-speed modulation works and why Xcel allows heating-based sizing.
3. No load calculation at all
Some contractors "eyeball" sizing based on square footage or what the old system was. This is guesswork, and it's not compliant with Xcel's rebate requirements.
Red flag: If no one measures your house, asks about insulation, or runs Manual J software, they're not doing it right.
4. Using the wrong design temperatures
Manual J requires using ASHRAE 99.6% design conditions for heating. In Denver, that's weather station based, typically 5 degrees F for winter, can be as low as -10 degrees F. Some contractors use milder assumptions, which undersizes the system.
Red flag: Ask what heating design temperature they used. If it's warmer than 5 degrees F for Denver metro, question it.
Understanding the Balance Point
The balance point is the outdoor temperature where your heat pump's capacity exactly matches your home's heat loss. Above this temperature, the heat pump handles everything. Below it, backup heat supplements the difference.
For a properly sized cold climate heat pump in Denver:
- Well-insulated home: Balance point around 0 degrees F to 5 degrees F
- Average insulation: Balance point around 10 degrees F to 15 degrees F
- Older home, poor insulation: Balance point around 20 degrees F to 25 degrees F
The lower your balance point, the less you rely on backup heat. Proper sizing pushes that balance point down, giving you more hours of heat-pump-only operation.
Why This Is a Good Thing
Xcel's requirements protect you:
- Maximum flexibility - Properly sized systems let you choose how much to rely on backup heat
- Future-proofing - Ready for changes in energy prices or regulations
- Rebate compliance - Improperly sized systems may not qualify for rebates
- Quality assurance - Xcel inspects installations, ensuring contractors do the job right
See Your Balance Point
Use this calculator to visualize how a heat pump's capacity compares to your home's heating load at different temperatures. The balance point shows when backup heat kicks in.
Balance Point Calculator
See where your heat pump meets your home's heating demand
Design load at -10°F (from Manual J calculation)
Balance Point
25°F
Backup heat kicks in below
Backup Heat Runtime
~750 hrs
15% of heating season
Heat Pump Coverage
85%
of heating hours
What This Means
Your heat pump is sized smaller than ideal for Colorado winters. With a balance point at 25°F, backup heat will run frequently during December-February. Consider a larger system for better efficiency and future flexibility.
Get a professional Manual J calculation for precise sizing tailored to your home.
Questions to Ask Your Contractor
Before signing a heat pump contract, ask:
- "Are you sizing for heating load or cooling load?"
Correct answer: Heating load (for cold climate/variable-speed systems) - "What design temperatures are you using for Manual J?"
Correct answer: Weather station based, typically 5°F for Denver winter, can be as low as -10°F - "What's the switchover temperature for backup heat?"
Should be a specific number they can explain and adjust - "Can you show me the Manual J load calculation?"
Should produce an actual document, not a guess - "What's the heating capacity of this unit at 5 degrees F?"
Should be at least 70% of rated capacity at 47 degrees F (Xcel requirement for cold climate designation)
The Bottom Line
Sizing a heat pump for cooling load is outdated. Warning about "oversized" variable-speed systems reveals a misunderstanding of the technology.
For cold climate heat pumps, Xcel requires sizing for heating load, with no oversizing penalty, because that's how you get a system that:
- Handles Colorado winters without leaning on backup heat
- Gives you flexibility as energy prices change
- Qualifies for rebates
- Runs efficiently instead of constantly triggering backup
If your contractor isn't following these rules, you may end up with a system that's permanently limited. Unable to meet your heating needs no matter how energy economics evolve.





